Hospital Heat Recovery Ventilation: Infection Control And Energy Recovery

Hospital ventilation has two competing requirements — a controlled, high air-change rate for infection control, and the lowest possible energy consumption for that air change — and heat recovery is how both are met at once: recovering 68–76% of the heat from the exhaust air means the plant only conditions the outdoor air rather than re-conditioning air the building has already warmed. ROTER supplied 880 ventilation units to Wuhan Huoshenshan Hospital during the emergency build, and has delivered equipment for the Heze Fangcang shelter hospital.



The energy argument for hospitals specifically


Hospitals run at high air-change rates by design. Isolation rooms, operating theatres, clean wards and laboratory areas all require the air to be changed frequently, which means a very large volume of outdoor air has to be conditioned around the clock.


Without heat recovery, that outdoor air is heated or cooled from scratch every time, and the heat is simply discharged. With a total heat recovery unit, the exhaust air gives up its sensible and latent heat to the incoming outdoor air before the mixing point, so the boiler and chiller handle a much smaller delta. In ROTER's measured case on a 200 m² room in Beijing, total heat recovery saved approximately 1,112 kWh in winter and about 1,427 kWh in summer — roughly 42.3% annually at ¥0.48/kWh.


The second point matters in healthcare: recovering heat also recovers moisture in a total heat core, so the supply air arrives closer to the required humidity and the reheat coil in the plant room does less work.



Choosing the equipment for a hospital duty


Hospital ventilation equipment selection

Hospital areaRecommended productReason
General wards, offices, public areasMedium ceiling-mounted total heat recovery unit1,000–15,000 m³/h, 68–72% efficiency, 57–75 dB(A)
Isolation and high-change-rate areasTotal heat recovery unitLatent recovery reduces both cooling load and reheat duty
Operating theatres and clean zonesPlate total heat exchangerNo moving parts in the airstream; complete stream separation
Large plant rooms, high duct pressureVertical total heat recovery unit75–76% sensible / 58–70% total published separately per model
Isolation rooms and storage requiring low dew pointRotary desiccant dehumidifier−70°C dew point capability
Existing plant replacementDC inverter total heat recovery ventilator40 dB(A), 70% efficiency, single-phase, PM2.5 removal rate 99.9%



Ventilation rate reference


The fresh air volume should be the larger of the minimum per-person rate and the air-change requirement. Reference figures from the ROTER product manual: general office 30 m³/h per person; high-grade office 30–50 m³/h per person; residence or villa 30–50 m³/h per person; shopping mall 15–25 m³/h per person. For air-change rate: general rooms 1–2 ACH; computer rooms 2–4 ACH; smoking-intensive meeting rooms 3–8 ACH. Hospital isolation and surgical areas normally follow the specific air-change schedule set for the room classification rather than this general table.



Published performance


CXH series — medium ceiling-mounted total heat recovery unit

ModelAirflow m³/hStatic pressure PaMotor power kWEfficiency %Noise dB(A)Weight kg
CXH-10DA10001200.447261140
CXH-25DA25002001.106859210
CXH-50DA50002702.747063350
CXH-100DA100004007.007172670
CXH-150DA1500040011.07075780


Test conditions (GB/T 21087): summer — outdoor dry bulb 33°C, RH 80%; indoor dry bulb 26°C, RH 50%. Winter — outdoor 0°C, RH 30%; indoor 20°C, RH 60%. Full 14-model range on the medium ceiling-mounted total heat recovery unit page.



Hospital project references


ROTER's medical project record includes the Wuhan Huoshenshan Hospital, which received 880 ventilation units, the Heze Fangcang shelter hospital, and the Construction Project of Medical Center at the New Campus of Yuncheng County People's Hospital. Published references are on the case study page, and the general range is on the product index.



Frequently asked questions


Do hospitals benefit from heat recovery ventilation?

Yes, and significantly, because hospitals operate at high air-change rates for infection control and continuously. Without recovery, every cubic metre of outdoor air is conditioned from scratch. ROTER's measured case on a 200 m² room showed approximately 42.3% annual energy saving with total heat recovery, at a documented 1,112 kWh winter and 1,427 kWh summer saving.


Does heat recovery compromise infection control?

No. A plate heat exchanger physically separates the supply and exhaust air streams, so there is no path for one to reach the other. A rotary heat exchanger likewise transfers heat through the rotor matrix without mixing the two streams. For the most sensitive areas, a plate total heat exchanger with zero cross-contamination is the appropriate specification, and the dehumidification can be handled separately by a rotary desiccant unit where a low dew point is required.


What fresh air rate does a hospital isolation room need?

Isolation and surgical areas follow the specific air-change schedule set for the room classification rather than a general table. For general areas, the ROTER product manual references are 30 m³/h per person for a general office, 30–50 m³/h per person for a high-grade office, and 1–2 ACH for general rooms, rising to 2–4 ACH for computer rooms. Send us the room volume, occupancy and required air-change rate and the sizing comes back with the calculation.


How many ventilation units did ROTER supply for Huoshenshan Hospital?

ROTER supplied 880 ventilation units to Wuhan Huoshenshan Hospital as part of the emergency build in 2020. That project is one of the largest single volumes in ROTER's record and is published with the equipment details on the case study page.


Can hospital ventilation equipment be supplied with test reports and CE documentation?

Yes. ROTER holds ISO 9001, ISO 14001 and ISO 45001 management system certification and CE certification for rotary wheel heat recovery units. Published efficiency figures are stated at GB/T 21087 conditions, and equivalent calculations at EN 308, EN 16798-3 or ASHRAE 220 conditions can be provided with the relevant test report and submittal package.