Products
  • Sensible heat plate heat exchanger (Cross-counter flow)

    Sensible heat plate heat exchanger (Cross-counter flow)

  • Sensible heat plate heat exchanger (Counter flow)

    Sensible heat plate heat exchanger (Counter flow)

  • Plate Sensible Heat Exchanger

    Plate Sensible Heat Exchanger

  • Plate Total Heat Exchanger

    Plate Total Heat Exchanger

  • Wheel Heat Exchanger

    Wheel Heat Exchanger

  • Heat Recovery Wheel Unit

    Heat Recovery Wheel Unit

  • U-Type Dehumidification Heat-Pipe Heat Exchanger

    U-Type Dehumidification Heat-Pipe Heat Exchanger

  • Heat Pipe Heat Exchanger

    Heat Pipe Heat Exchanger

Air Heat Exchangers for Ventilation Energy Recovery

A heat recovery exchanger sits in the middle of a ventilation system: supply air and extract air pass through it in separate channels, and the heat in the outgoing air is transferred to the incoming air. The result is fresh air delivered without the full air conditioning load that would otherwise be needed to condition it. ROTER manufactures three core types, each with a different working principle, and supplies them both as cores and as complete units.

The three core types

1. Plate heat exchanger

Two air streams are separated by thermally conductive plates and heat passes through them by conduction. Supply and exhaust air never mix, so odour and moisture cannot transfer between them. ROTER plate cores use high quality hydrophilic aluminium foil or epoxy-coated aluminium foil; the foil carries a coating that wets readily, so condensate flows down the surface instead of bridging the channel and reducing transfer.

2. Rotary heat exchanger

A honeycomb rotor rotates continuously at 10 rpm and acts as a heat and cold storage core. Fresh air passes through one semi-circle while exhaust air flows counter-currently through the other, so the two streams exchange heat through the same rotating matrix. Up to 75% of the thermal energy in the exhaust air can be recovered. ROTER builds the rotor cores, the molecular-sieve desiccant and the aluminium foil process directly from United States sourced technology, in a range of specifications.

For industrial exhaust streams above 120°C, an ECW type high temperature rotor rated to 300°C is available, with cores made of magnesium-aluminium alloy or stainless steel foil.

3. Heat pipe heat exchanger

A gravity heat pipe has no moving parts and cannot leak. The evaporator section absorbs heat from the hot airflow; the vapour generated inside the pipe travels to the condenser section, where the cold airflow takes the heat back and the condensate returns by gravity. A U-type arrangement places the evaporator and condenser sections horizontally on either side of the air handling unit evaporator and connects them with copper tubes, which is the configuration used for dehumidification.

Which type to choose

Requirement Recommended core Why
Fresh air must not pick up any odour from exhaust Plate Physically separated air paths with a solid barrier
Maximum heat recovery from high volume exhaust Rotary Up to 75% recovery in a compact core
Condensate-free operation, minimal maintenance Heat pipe No moving parts, no water circuit to leak
Humidity must be removed from the supply air Plate total or desiccant wheel Latent heat transfer, not sensible heat only

What the recovery is worth

In a 200 m² room case documented in the ROTER manual, outdoor air at 33°C is supplied at about 28°C instead of the 7°C that ordinary ventilation would require, saving approximately 1,112 kWh in winter and 1,427 kWh in summer, an annual saving of roughly 42.3% at 0.48 CNY per kWh. Because the load on the air conditioning equipment falls, the installed equipment size can often be reduced as well.

Inquiry Form

We will respond via email within 24 hours. Please keep your contact information available.